Meeting Nov 16·Meeting recap

Earl Township Adopts Data Center Law: 250 Feet From Homes

Earl Township adopted Ordinance 2026-2 on Nov. 16. Data centers may seek approval only in its small Industrial District, on 15+ acres. None is proposed.

The Berks Beat|Published November 20, 2026
Earl Township
Illustration for Earl Township Adopts Data Center Law: 250 Feet From Homes

Earl Township's supervisors adopted a data center law on Monday, Nov. 16. It lets a data center seek approval only in the township's small Industrial District, under rules the board calls stringent. No data center is proposed there.

What it means for you

  • A data center would have to stay at least 250 feet from any house.
  • No project is on the table. The board says the law "does not approve the construction of a data center."
  • Any future proposal would need a public hearing before the supervisors, where residents can speak.
  • A builder would have to supply noise and water studies and pay to train local firefighters.
  • If a data center shuts down, its owner must clear the site and set aside money in advance to pay for it.

What passed and what the board says it means

An ordinance is a local law a municipality adopts. The signed ordinance, Ordinance 2026-2, takes effect "immediately after enactment." The township posted it on its homepage with a notice from the board.

The notice says the township "is legally obligated to permit data centers." It adds that the township can still set rules for where and how. The board says the law sets "a designated, limited area" with "stringent regulations." It ends: "There is no data center proposed for Earl Township at this time."

The law covers more than server farms. Its definition includes buildings for artificial intelligence, cryptocurrency mining and blockchain processing. It does not cover a few servers inside an ordinary office.

All three supervisors signed the ordinance. The township secretary attested it, meaning the secretary signed to confirm it. The signatures do not show how each supervisor voted.

The secretary also signed a certificate of enactment, a page confirming the board adopted it. It says the board adopted it at a public meeting on Nov. 16. The township has not posted the November minutes. So the vote count and what residents said at the hearing are not on the record yet.

The law took months to reach a vote. In July, the board voted to send the draft to the Berks County Planning Commission, the July minutes show. That county board reviews local zoning changes. In October, the solicitor's report said the hearing and vote would come in November, per the October minutes. Our preview covered the agenda.

Only in the Industrial District, by conditional use

The law adds data centers to the list of conditional uses in the Industrial District. A conditional use is a use the zoning ordinance allows in a district only after the supervisors hold a hearing and find it meets the ordinance's conditions. In short, a builder must ask, and the board must hold a hearing first.

The Industrial District is the zone the township's zoning ordinance sets aside for "light industrial and manufacturing uses." It is small. The township's posted zoning map shades it in the southeast corner, along Boyertown Pike (Route 562) at the Douglass Township line. Most of the rest is the Woodland Agricultural Conservation district. There is also a Highway Residential strip along Route 73 and a landfill district.

The posted map's certification block, where officials sign and date it, is blank. So the official copy is the one at the township office.

The posted map does not show distances to individual homes. No township document says whether any parcel in the district has the 15 acres the law requires.

How big a data center can be

The law sets these size limits:

  • Lot: at least 15 acres.
  • Building: no more than 100,000 square feet each.
  • Number: no more than three buildings in one development.
  • Height: 45 feet, plus 15 feet for rooftop equipment such as cooling towers.
  • Spacing: buildings at least 50 feet apart.
  • Parking: the law gives two ways to count spaces, and the larger count applies.
  • One way is two spaces for each worker on the largest shift.
  • The other way is one space for each 500 square feet of building.
  • Ten visitor spaces are added on top.

The height limit is higher than the 35-foot cap for other buildings in the Industrial District, set in the zoning ordinance. The new law says its rules win where the two conflict.

Equipment such as substations, cooling towers and backup power must sit in the rear yard, behind the building. Generators and cooling units go on the side of the building that faces away from homes.

How far from neighbors

The law sets these distances:

  • 100 feet from any lot line and any road right-of-way, the strip of land a road sits on.
  • Parking lots, loading areas and driveways are the exception. They may come as close as 15 feet to a lot line.
  • 250 feet from any house.
  • 250 feet from the edge of the township's two residential zones.
  • 1,000 feet from any school, cemetery, church, licensed daycare or historic structure named in the township's comprehensive plan, its long-range land-use plan.
  • 1,000 feet from a data center on another property.

The two residential zones are WAC, the Woodland Agricultural Conservation district, and HR, the Highway Residential district. The law uses only the letters. The full names come from the township's zoning ordinance.

A buffer must stand between a data center and homes or roads. It is an earth berm averaging at least 5 feet high, planted with evergreen and leafy trees. Frontage here means the lot's edge along a road or a neighboring home lot. The law calls for at least one of each tree for every 20 feet of frontage.

The buffer must go in when construction starts. The township can allow a different timing during its review of the building plans.

Noise limits

Decibels measure how loud a sound is. A higher number means a louder sound. The law measures sound on the neighbor's property, not at the data center. Near homes, schools, churches and similar places, the limits are:

  • Daytime, 7 a.m. to 7 p.m.: an average of 50 decibels, on the scale the ordinance uses, with peaks up to 60.
  • Night, Sundays and holidays: an average of 45 decibels, with peaks up to 55.
  • Next to businesses or parks: a daytime average of 60 and a night average of 55.

A builder must file noise studies three times: with the application, during building review and after the center opens. An acoustics expert must do each one, and the builder pays. If the township finds a violation, the owner must fix it promptly.

Backup generators running during a power outage are exempt. The limits apply again within three hours after power returns. No vibration a person can feel may reach past the property line.

Water, sewer and cooling

A data center must use public water and public sewer. It may not drill its own well.

The builder must show the water supply is enough. A study by a licensed engineer or geologist must map wells and streams within 1,000 feet. No data center may be approved unless the study shows it will not hurt nearby wells or streams. It also may not raise water or sewer rates for other customers.

Cooling must be a closed-loop liquid system, which reuses the same fluid. Air cooling may not be the main system. Fluid drained from the cooling system must be hauled away. It may never go into the sewer or storm drains.

Some projects use a lot of water. They may also need approval from the Delaware River Basin Commission, an interstate agency that manages water in the river's basin. The law requires that approval when a project's water use passes the commission's limits.

Power and backup generators

The builder must file an agreement from the electric company showing it has enough capacity. The application must also note any known effect on other customers' electric rates. The center must run on the power grid, not on its own power plant. The builder must also pay to extend or upgrade water, sewer, gas, power and other utility lines.

Backup generators must burn natural gas from utility pipes only. No gas may be stored on site. The rules for generators:

  • Testing is capped at 100 hours a year.
  • No testing on days the air quality is rated unhealthy.
  • One exception is allowed. The law calls it a "grid-declared emergency."
  • The law does not define that term.
  • No running them to cut power costs or for other non-emergency use, unless the board approves.
  • Generators and exhaust stacks must be 1,000 feet from schools, churches and similar places.
  • They must also be 250 feet from a home's lot line and 150 feet from other lot lines.
  • They can be closer only if air modeling shows the exhaust will not break air-quality standards.
  • Air modeling is a computer study of where the exhaust goes.

A megawatt is a measure of power output. A center with more than 1 megawatt of backup power must file an air study. The board may require air monitors at the property line.

Large battery systems must contain spills. The site must also catch all the water used in an 8-hour fire, so toxic runoff stays out of storm sewers, streams and groundwater.

Fire and emergency rules

A qualified professional must write an emergency response plan. The township's building code official and the local fire chief must approve it. The law also requires:

  • A Knox Box, a lockbox that lets firefighters get in fast.
  • A second way in and out for emergency vehicles.
  • Roof access from inside and outside.
  • Yearly training for local firefighters and ambulance crews, at the owner's expense.
  • Any special firefighting gear the center needs, given to local crews.
  • Emergency contact names and phone numbers on file with the township and county 911.

The operator must also file a pollution plan before opening. It lists every regulated substance kept or used on site and how spills are handled. The plan is updated every year.

When a data center closes

The owner must take down a closed data center within six months, at its own cost.

The law has a test for when a center is done. The test compares the center's power use to its peak, meaning its highest power use. The law does not say over what period the peak is set. If use stays below half the peak for a full year, the center is presumed closed.

The owner must get the electric company to agree to tell the township within 30 days whenever power use falls below half its peak.

A zoning permit is the township's permit to use land a certain way. The owner must file a cleanup cost estimate by the time that permit is issued. It must then keep a bond or similar guarantee for at least 125 percent of the cleanup cost, after subtracting the equipment's resale value. A bond is money or a pledge the township can use if the owner does not clean up. The estimate is updated every five years.

If the owner does not finish, the township can do the work. It can then use the bond money. For any cost above that, it can place a lien on the owner's property. A lien is a legal claim on the property until a debt is paid.

A traffic rule for all development

The ordinance also rewrites the township's traffic study rule. That rule covers all new development, not only data centers.

The township's posted 2017 zoning code required a traffic study for business projects of 20,000 square feet or more. It also required one for any project expected to add more than 1,000 trips a day. The new rule drops both tests. It counts only vehicle trips in the busiest hour, starting above 50.

The data center rules ask for a traffic study only "if required" under this rule, the ordinance says. So a data center with few workers may no longer need one. The new rule also drops the board's power to demand a study in other cases. The board must still find that a conditional use will not cause hazardous or congested traffic, the zoning ordinance says.

Under the new rule, a project needs a study at these sizes:

  • Short study, homes: a project with 15 or more homes or lots.
  • Short study, businesses: a project adding more than 50 but fewer than 100 vehicle trips in the busiest hour of the day.
  • Full study, homes: a project with 25 or more homes or lots.
  • Full study, businesses: a project adding 100 or more vehicle trips in the busiest hour of the day.

What happens next

Minutes are the board's written record of a meeting. The board approves each month's minutes at the next meeting. The October minutes show this. So the record of the Nov. 16 vote and hearing should come up for approval Dec. 21. The township's minutes page runs through October.

A company that wants to build would apply for conditional use. That means a public hearing before the supervisors, where residents can speak. Neither the new law nor the zoning code pages we read say how residents would be told about such a hearing.

By our count from our data center tracker, Earl is at least the 15th Berks municipality to adopt data center rules. Earl's board met last month on a trash contract.

Other business on the Nov. 16 agenda

The agenda also listed a resolution on a revised land development plan for 1552 W. Philadelphia Ave. It named no applicant or project. No posted record shows the outcome.

The township engineer was also to update the board on the Hill Road storm sewer. No posted record shows what was said. In July the board hired Barrasso Excavation to do that work for $147,757, due by Oct. 31, the July minutes show.

The township Planning Commission canceled its Nov. 19 meeting, the agenda says. Its next meeting, if needed, is Dec. 17.

When and where

  • Next supervisors meeting: Monday, Dec. 21, 7 p.m., per the November agenda.
  • Place: Earl Township Municipal Building, 19 Schoolhouse Road, Boyertown.
  • The board meets on the third Monday of each month at 7 p.m., per its board page.

How to comment

  • Speak during public comment, early in each monthly meeting.
  • Call the township office: 610-367-9673, 8 a.m. to 4 p.m. weekdays.
  • Email: Earltwp@earltwpberks.com.
  • Read the ordinance on the township homepage.

Also at the meeting

  • The agenda also listed approval of the Oct. 19 minutes, the treasurer's report and the bills. The outcomes are not yet on record.
  • The ordinance is signed on the lines for the chairman, vice chairman and member; the board page names them as William Moyer, Michael Marburger and John Cleaver. Secretary Janice Haller signed to confirm it and signed the certificate of enactment, dated Nov. 16.
  • The township posted the ordinance as a scanned file with no searchable text.

Keep reading

More local reporting from around Berks County.

Meeting preview

Amity Holds Tax at 3.05 Mills; Fire, EMS Taxes Rise

Amity Township's proposed 2027 budget keeps the general tax at 3.05 mills but raises the fire and EMS taxes. The supervisors vote Dec. 16.

Meeting recap

Berks Proposes 3.7% Tax Hike: $33 More Per $100K Home

Berks County's proposed 2027 budget would raise the county tax 3.7%, or $33.30 a year per $100,000 of assessed value. The commissioners vote Dec. 17.

Meeting preview

West Reading Drafts Half-Mill Tax Hike, $50 on $100K Home

West Reading posts a 2027 tax ordinance at 10.25 mills, up a half mill, plus data center and police pension laws. Council votes on all of them Dec. 15.

Meeting recap

Mohnton Plans 0.75-Mill Tax Hike, Drops Ladder Truck Grant

Mohnton council voted to advertise a 2027 tax ordinance adding 0.75 mill for property and 0.25 for fire, and dropped a ladder truck grant bid.

MohntonNov 20
Meeting preview

Union Township Votes on 2027 Budget, Names 2 Fire Companies

Union Township supervisors vote tonight on a 2027 budget with no figures online, name two official fire companies from Jan. 1 and pay $173,333 for paving.

Meeting preview

Robeson Township Weighs Budget Ad and Volunteer Tax Credit

Robeson Township votes Thursday on advertising an unposted 2027 budget and takes up a volunteer tax credit, fire-company items and a sewer hookup.

All Berks County news →